fire alarm control panel power supply

NFPA 72, National Fire Alarm and Signaling Code specifies the power requirements for fire alarm systems.

A system must have either two sources of power (primary and secondary) or a single Uninterruptible Power Supply (or UPS). Where primary and secondary power supplies are used, the secondary supply can consist of batteries or batteries plus a standby generator.

Altronix AL1042ADA220 NAC Power Supply - 4 Class A or 4 Class ...

NFPA 72 requires that the circuit disconnecting means be labeled “fire alarm”. The marking must be red in color.

For a basic fire alarm system that uses primary power with batteries only as secondary power, the battery capacity must be sufficient to operate the system in a non-alarm condition for a minimum of 24 hours.

The Code requirement for 15 minutes of full load should be considered in conjunction with performing a risk analysis to determine if a larger capacity is needed.

Leave a Reply

This site uses Akismet to reduce spam. Learn how your comment data is processed.

Discover more from My Engineering

Subscribe now to keep reading and get access to the full archive.

Continue reading